Duct bank: one feeder becomes four
An end view of a duct bank in the ground. Each added conduit leaves every fill ring exactly where it was, but the harness derates the whole bank with one number, and that line sinks through the feeders until the first one is over it. Pick a story to see what helps and what does not, or switch to free play and tap the dashed circles to add conduits.
Story
Free play · every number is one cell of the exported grid or tables
Conduits per row
Rows
Conduit
Cables per conduit
Cable
Clear gap between conduits
Soil resistivity, C cm/W
Burial to top of bank
Earth ambient
Encasement
Controls snap to the values the harness was run at; nothing between them is estimated. The dashed circles on the drawing add a column or a row, and show the ampacity the grid holds for that bank.
Duct bank · end view of the trench, bank and conduits
Bank ampacity vs feeder loads
Ampacity by bank shape · same cable, soil, burial and ambient
Every check at this step · the controlling row is highlighted
Rule column: the citation the data file gives for each check. None of these limits is checked against a published standard here.
How the checks read it
Every check · the problem, the change, the fix
Required values are the functions' own defaults for these cables, read from the data file: the fill limits and the grouping source have no checked citation. A row marked value is a number the function returns with no verdict. The feeder row is the exporter's own comparison against invented loads.
design_duct_bank_layout, calculate_conduit_fill, calculate_duct_bank_ampacity, calculate_trench_dimensions, calculate_concrete_encasement.Not modeled: heat flow between conduits or between banks, spacing as an input to ampacity (the function has none), encasement as an input to ampacity, a thermal-backfill model (a lower soil resistivity number is the only stand-in), cooler ground at depth, per-conduit ampacity (one number covers the whole bank), cable pulling, vault sizing, and any standards-based limit. The conduit trade size is used as the drawn diameter, the conduit wall is drawn at a fixed width so it can be seen, and the street, soil and trench art are a fixed illustrative backdrop.See also:Duct bank, hands-off walkthrough · Cable pull, vault to vault · Conduit fill