Research — Auto Demo · Precomputed (draft, unvalidated)
Bus scheme and breaker count — auto
No controls here: seven short stories play on their own. A single bus loses everything when its bus or a stuck breaker goes. A ring loses two circuits to one stuck breaker. Breaker-and-a-half loses nothing to a bus fault but one or two circuits to a breaker that will not clear. Double breaker and main and transfer buy their way out with more breakers. An odd breaker-and-a-half has no exact target and nothing is drawn. Use Pause, or the story and step buttons, to stop on any frame.
Story
Substation one-line · illustrative geometry, not a design
A circuit counts as energized when it is connected to a live source; a supply circuit also needs another circuit terminal in its component, so a source cut off from the station delivers nothing.
Circuits · which ones survive
Breaker bay · installed against what the harness requires
One slot per breaker. The dashed tick marks the harness’s required count for this scheme and circuit count; a dashed slot is a breaker the count wants and the bay lacks, a red one is beyond it.
Compare the schemes · same circuit count, same failure
Every check at this step · the controlling row is highlighted
Rule column: the citation the data file gives for each check.
How the checks read it
Every check · before, the step, the fix
The breaker count is the harness's result. Circuits still energized is demo logic from the exporter's graph walk. There is deliberately no whole-station verdict. Incomplete means the harness has no exact target and skipped the check: it is never a pass.
required_breaker_count, check_bus_configuration_breaker_count.Not modeled: real outage statistics or reliability, protection and relay coordination, breaker and bus ratings, fault current, maintenance switching, double-failure cases, and any real station layout. The drawing is schematic.See also:Bus scheme and breaker count, interactive with free play · Station walk, hands-off