Typed, cited cooling and fluid-sizing calculations for AI datacenters.

Compute-only functions for liquid and air cooling design: heat-load aggregation, cooling-capacity margin, pump-curve and flow-rate-curve evaluation, pipe velocity and inlet-air envelope checks. Each returns a typed value with provenance. They never judge whether a result is acceptable, and equipment data is passed in by the caller.

Interactive demos

Harnesses in action

Scripted chat-and-viewer examples where this domain's harness is one of the tools. Illustrative, not live sessions.

All harness demos →

What it can do

  • aggregate_rack_heat_load

    Aggregates rack heat load into a typed total.

  • check_cooling_capacity_margin

    Demand kW against summed cooling-unit capacity; negative margins are returned, not raised.

  • evaluate_quadratic_pq_curve

    Evaluates a quadratic pump pressure-flow curve and flags out-of-range queries.

  • interpolate_flow_rate_curve

    Interpolates a flow-rate curve and flags out-of-range queries.

  • evaluate_pipe_velocity_for_flow_rate

    Pipe velocity from flow and diameter, checked against cited small- and large-pipe limits.

  • check_inlet_air_temperature_envelope

    Inlet air temperature against ASHRAE envelope classes.

A worked case

Input

1,000 kW demand against one liquid cooling unit rated at 1,368 kW.

Result

Margin of +368 kW (36.8%). At 2,000 kW demand the margin comes back as −632 kW rather than raising an error.

Where this stands

Draft; no mechanical or thermal engineer has reviewed it yet. An audit of the input data caught real discrepancies, and the functions use whatever value a caller passes without correcting it. Pipe-velocity limits are cited to ASHRAE through secondary sources only.

Open questions

  • Pump-curve against system-curve intersection is not built.
  • A full pressure-drop-versus-diameter formula, beyond the velocity check, is open.
  • Capacity margin is scalar-only, so it cannot confirm a unit delivers nameplate capacity at actual flow and temperature.