Research — Illustrative (draft, unvalidated)
Insulator swing vs wind
Pick wind pressure, line angle, tension and vertical span for a suspension string, and watch it swing toward the structure. Enter your own allowable swing angle to see the vertical span that would hold it. The bulletin's TH-10 161 kV cases are one click away as presets.
Elevation looking along the line · suspension string swinging toward the structure (schematic)
Bulletin TH-10 161 kV cases · sets tension, wind and limit
Wind pressure
Line angle
Conductor tension
Vertical (weight) span
Horizontal (wind) span
Allowable swing angle · yours to enter
The bulletin's TH-10 example values (Table 7-2): 16.4° no wind, 53.2° moderate wind, 77.7° high wind. Your structure's limit may differ.
Insulator swing
Swing angle
Vertical span for the entered limit
Against your limit
How the check read it
insulator_swing_angle_deg, required_vertical_span_ft, conductor_wind_load_per_foot.Not modeled: the clearance table the swing is meant to be compared against (Bulletin Table 7-1), the structure geometry, and the allowable swing limit, which is YOURS to enter: the 16.4°, 53.2° and 77.7° values are shown only as the bulletin's TH-10 example values (Table 7-2, 161 kV, 10 insulators). Conductor and string are fixed to the worked example's 795 kcmil 26/7 ACSR (1.108 in, 1.0940 lb/ft) and a 135 lb string. Wind is assumed blowing toward the structure; temperature, ice and span sag are not modeled. The drawing is schematic: only the angle and force ratio are computed.See also:Insulator swing, auto sweep · Pole groundline moment, interactive