Ampacity, fault current, grounding and sheath-bonding calculations — two anchored to published examples.

Typed calculation functions for distribution-side electrical engineering: conductor and underground-cable ampacity, symmetrical-components fault current, IEEE 80/81 grounding, and cable sheath induced voltage and circulating-current loss. Each result carries provenance (cited method, version, timestamp) and the functions compute values without judging acceptability.

IEEE 80 · IEEE 81 · IEEE 1453 · NEMA MG 1

Interactive demos

Harnesses in action

Scripted chat-and-viewer examples where this domain's harness is one of the tools. Illustrative, not live sessions.

All harness demos →

What it can do

  • calculate_conductor_ampacity

    Steady-state bare overhead conductor ampacity from ambient, wind, solar and max conductor temperature (IEEE 738).

  • calculate_underground_cable_ampacity

    IEC 60287-1-1 / Neher-McGrath ampacity for a single direct-buried cable.

  • calculate_available_fault_current

    Three-phase, line-to-line and single-line-to-ground fault current from a source plus path impedance.

  • calculate_grounding_grid_resistance

    Grid resistance using Sverak’s formula, IEEE Std 80-2013.

  • calculate_ground_potential_rise

    Decrement factor, grid current and ground potential rise.

  • calculate_sheath_bonding_loss_factor

    IEC 60287-1-1 circulating-current sheath loss factor for solidly bonded cables.

A worked case

Input

Drake 795 kcmil 26/7 ACSR at 100 °C max conductor temperature, 40 °C ambient, 2 ft/s crosswind, solar flux 96 W/ft².

Result

The harness computes 980.5 A, which is 1.3% under the ~993 A that IEEE Std 738-2012 Annex B publishes for this case and inside the test’s ±10% band. Because the 100 °C limit is above the tabulated range, the conductor resistance is extrapolated, not interpolated, so even this one published anchor is partly extrapolated.

Where this stands

Draft; outputs should not feed compliance decisions until reviewed. Only conductor ampacity and the transformer hottest-spot function are anchored to an independent published reference; the grounding decrement and surface-layer factors each match one published point. Everything else is tested for internal self-consistency only.

Open questions

  • Cable fault-withstand K factors are flagged unverified, with a likely non-conservative error left unchanged pending a primary source.
  • No IEEE 80 Annex worked example could be recovered, so the grounding chain has no full independent benchmark.
  • Sheath loss models circulating current only (no eddy, armour or cross-bonding) and is not yet composed into the ampacity function.